MEW00290 Rev: 1
8
Technical Description External Presentation unit 1728
Commissioning a new unit / SSD
download
The 1582 / 1587 board shall be mounted in the EBL512 c.i.e. and the
fuse "F1" shall be removed. The cable (RS485 line) to the ext.
15
Presentation unit(s)
shall be connected.
The EBL128 c.i.e. shall be powerless and the "RS485 transceiver
component 4552" shall be plugged on the main board. The cable
(RS485 line) to the ext. Presentation unit(s)
The SW mode and the address have to be set in each new unit
according to chapter "SW mode & Address setting", page 11. Here
follows a brief summary (a recommended sequence of actions):
1. Connect the cable from the c.i.e. to the ext. Presentation unit's
terminal block.
2. When all connections are done put back the fuse "F1" on the
1582 / 1587 board in the EBL512 c.i.e. / power up the
EBL128 c.i.e., i.e. the ext. Presentation unit(s) will now be
powered up.
3. A brand new unit will automatically be ready for the SW mode
setting.
4. After SW mode and address setting press "P2" (yellow) and the
unit will restart, see chapter "Restart", page 18.
5. Since the SSD is not downloaded in the c.i.e. there will be a
fault message in the ext. Presentation unit's display:
"
No contact with Control unit
All LED:s in the ext. Presentation unit will be turned off.
6. Now the SSD have to be downloaded via Win512 / Win128.
Connect the PC to the c.i.e.
download SSD" dialog box, verify that the "Download FBP /
AAU" checkbox is marked. Start the download of SSD.
7. After download of SSD to the c.i.e. it will restart and the
download of SSD to the ext. Presentation unit(s) will take
place.
During this download will be shown:
"SSD download in progress....."
15
One or more ext. Presentation units and/or ext. FBPs and/or Alert
Annunciation Units can be connected.
16
Via Win512 is the 1582 / 1587 board programmed (incl. its address). Via
Win512 / Win128 is each unit (e.g. an ext. Presentation unit) programmed
regarding the Address, Selective alarm presentation and if the buzzer should
be disabled. When required, also "User definable text messages" (alarm
texts).
15
shall be connected.