Object
Byte.Bit Range of values
number
194 3
[0]: No action
[1]: Trip without restart
[2]: Trip with restart
[3]: Trip end position
CW
[4]: Trip end position
CCW
[5]: Group warning
[7]: Emergency start
(not during ATEX
operation)
[8]: Motor CW
[9]: Motor CCW
[11]: Quick Stop
(direction-independent)
[12]: Trip RESET
[13]: Cold start (not
during ATEX
operation)
[14]: Quick Stop
clockwise
[15]: Quick Stop
counter-clockwise
[37]: Operational trip
end position CW
[38]: Operational trip
end position CCW
195 4
See input 1 - action
[9]: Motor CCW
(default for reversing
starters)
196 5
See input 1 - action
[13]: Cold start (default
for HF motor starters)
2 6 - 7
0.1 ... 12 A/10 mA
The maximum current
is preset.
15 8
18.75 ... 100%/
3.125% [6 ... 32]
[0]: Deactivated
16 9
50 ... 400%/
3.125% [16 ... 128]
[0]: Deactivated
1) As of Firmware version V1.2.0
Motor starter (3RK1308‑0**00‑0CP0)
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003
Meaning
Input 1 action
Input 2 action
Input 3 action
Rated operational current I
The rated operational current is
MLFB-dependent, and thus also the
maximum setting range.
Lower current limit
Upper current limit
A.12 Read/write DS201 device parameter 1
See Chapter ...
Inputs (Page 104)
Inputs (Page 104)
Inputs (Page 104)
Rated operational current
e
(Page 67)
Upper/lower current limit (Page 94)
Upper/lower current limit (Page 94)
Data sets
195