Process image of the inputs
Table 7- 2
Process image of the inputs (in bytes 0 to 3)
Process data
Meaning
DI 0.0
Ready (automatic)
DI 0.1
Motor ON
DI 0.2
Group fault
DI 0.3
Group warning
DI 0.4
Input 1
DI 0.5
Input 2
DI 0.6
Input 3
DI 0.7
Input LC
DI 1.0
Motor current I
DI 1.1
Motor current I
DI 1.2
Motor current I
DI 1.3
Motor current I
DI 1.4
Motor current I
DI 1.5
Motor current I
DI 1.6
Manual local mode
DI 1.7
-
DI 2.0
Ready to start for motor ON
DI 2.1
Motor ON - RIGHT
DI 2.2
Motor ON - LEFT
DI 2.3
Quick stop active
DI 2.4
Energy saving mode active
DI 2.5
DI module inserted
DI 2.6
Explosion protection of the motor active
DI 2.7
Parameter block active
DI 3.0
Thermal motor model overload
DI 3.1
-
DI 3.2
I
current limit tripping
e
DI 3.3
F-DI status
DI 3.4
Residual current detected
DI 3.5
Asymmetry detected
DI 3.6
Overtemperature
DI 3.7
-
1) From FW Version 1.2.0
Motor starter (3RK1308‑0**00‑0CP0)
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003
[%] bit 0
curr
[%] bit 1
curr
[%] bit 2
curr
[%] bit 3
curr
[%] bit 4
curr
[%] bit 5
curr
Parameters/address space
Relevant for
All
All
All
All
All (with 3DI/LC module)
All (with 3DI/LC module)
All (with 3DI/LC module)
All (with 3DI/LC module)
All
All
All
All
All
All
All (with 3DI/LC module)
-
All
All
Reversing starters only
All
All
All
Fail-safe starters only
All
1)
All
-
All
Fail-safe starters only
All
All
All
-
7.8 Address space
159