Siemens 3RK1308‑0 00‑0CP0 Series Equipment Manual page 115

Industrial controls et 200sp motor starter
Table of Contents

Advertisement

Example
The following example shows the "trip end position CW" with digital input 1 parameterized to
"Trip end position CW":
Figure 6-20
You switch the motor on by means of "Motor CW". The motor is running.
You switch the motor on by means of "Motor CW". The motor is running. The motor is switched off by
setting the digital input 1 (parameterized to input action 1 = Trip end position CW). A group fault is
generated at the same time by the starter. To switch the motor back on again, digital input 1 and the
signal "Motor CW" must be reset again. Thereafter you can start the motor again via the signal "Motor
CW". The group fault is deleted when the signal "Motor CW" is canceled.
You switch the motor on by means of "Motor CW". The motor is switched off by setting the digital input
1 (parameterized to input action 1 = Trip end position CW). A group fault is generated at the same time
by the starter. While digital input 1 is set, you can only run the motor counter-clockwise. The group
fault is deleted when the signal "Motor CW" is canceled.
You switch the motor on by means of "Motor CW". The motor is also switched off by setting the digital
input 2 (parameterized to input action 1 = Trip end position CCW). A group fault is generated at the
same time by the starter. While digital input 2 is set, you can only run the motor clockwise. To switch
the motor back on again, digital input 2 and the signal "Motor CW" or "Motor CCW" must be reset
again. Thereafter you can start the motor again via the signal "Motor CW". The group fault is deleted
when the signal "Motor CW" is canceled.
Motor starter (3RK1308‑0**00‑0CP0)
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003
Example of trip end position CW
6.15 Trip emergency end position CW
Functions
115