Functions
6.21 Quick Stop direction-independent
Example 2: Input 1 signal = non-retentive
122
The motor is switched on and off by "Motor CW".
The motor is switched on by "Motor CW", then switched off by the level at digital input 1
(parameterized with input action 1 = Quick Stop). The Quick Stop function is reset by Disable
quick stop. The motor is switched on again since "Motor CW" is still active.
The motor is switched off by the level at digital input 1. The "Quick Stop" function is reset by
setting "Disable quick stop". As the level "Motor CW" is still active, the motor runs "CW" again
until the "Disable quick stop" command is revoked.
Motor is switched on by "Motor CW", then switched off by the level at digital input 1. While the
"Quick Stop" function is active, the motor remains switched off and starts up again when
"Quick Stop" is revoked until "Motor CW" is switched off.
Motor starter (3RK1308‑0**00‑0CP0)
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003