Table 6- 8
Input n action
Input
Input n level
n action
No action
Trip without restart
Trip with restart
(AUTO RESET)
Trip end position
CW
Trip end position
CCW
Group warning
Emergency start
Motor starter (3RK1308‑0**00‑0CP0)
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003
Input n signal
NO/NC
n. ret./ret.
NO/NC
n. ret.
NO/NC
n. ret.
NO/NC
n. ret.
NO/NC
n. ret.
NO/NC
n. ret./ret.
NO
n. ret.
Operating
mode
All
No direct action on the motor starter. Evaluation
und further processing possible using the
process image.
All
Results in tripping of the motor.
Must be acknowledged once the cause of
the tripping has been rectified (initial status).
All
Results in tripping of the motor.
Acknowledged automatically after the cause
of the trip has been rectified (initial status).
All
The motor is switched off regardless of the
direction of rotation.
A fault is generated and reported.
The motor can only be switched on with
"Motor CCW"
All
The motor is switched off regardless of the
direction of rotation.
A fault is generated and reported.
The motor can only be switched on with
"Motor CW"
All
The diagnosis "Group warning" is output.
The motor starter is not switched off.
All
Starts the load when an ON command is
issued despite the fact that an internal trip
command is present.
Intrinsic device protection of the motor
starter remains active and prevents the
device from being destroyed.
Only allowed as a NO contact
Not parameterizable when the "EX motor"
parameter is active.
Functions