The supported object numbers and their meaning are shown in the table below:
Table A- 5
Assignment of object number to event message
Object No. Event messages
327 Thermal motor model overload
337 Residual current detected
340 ± Asymmetry detected
351 Input warning
365 Invalid parameter value
366 Parameters cannot be changed in ON state
1541 ± I
warning threshold exceeded
e
1542 ± I
warning threshold undershot
e
310 ± Emergency start active
357 Automatic mode
358 Manual bus mode
359 Manual local mode
360 Manual bus mode
368 ± Parameters block CPU/master active
376 Firmware update successful
378 Firmware update has errors
454 Internal communication fault
1520 ± Energy-saving mode active
1580 Switching element hot
±: Event is entered as "incoming" (+) and "outgoing" (-) event. Other messages are entered only as "incoming" messages
Motor starter (3RK1308‑0**00‑0CP0)
Equipment Manual, 11/2019, A5E34821005002A/RS-AC/003
Comment
Warnings
In the case of a group fault, the message
"Motor overload trip" is also queued.
-
-
-
Not in the case of startup since it is a
group fault
-
-
-
Actions
-
Enter at the time of changeover
Enter at the time of changeover
Enter at the time of changeover
Connection abort
-
-
-
-
-
-
A.7 DS75 logbook - Read events
Data sets
185