Trane CCUN 205-211 User Manual page 30

Chiller control system
Table of Contents

Advertisement

Comm Loss:
Suction Pressure Transducer
Comm Loss:
Ext Chilled/Hot Wtr Setpoint
Comm Loss:
External Demand Limit
Setpoint
Comm Loss:
Auxiliary Setpoint Command
Comm Loss:
High Pressure Cutout Switch
Comm Loss:
Evaporator Water Flow Switch
Comm Loss:
Condenser Water Flow Switch
Comm Loss:
Local BAS Interface
Comm Loss:
Solenoid Valve
Comm Loss:
Motor Temp/Overload
Comm Loss:
Compressor Run Command
Comm Loss:
Protection Module Cprsr
30
Diagnostics
Circuit
Immediate
Latch
Chiller
Warning
Latch
and Special
Action
Chiller
Warning
Latch
and Special
Action
Chiller
Warning
Latch
and Special
Action
Chiller
Immediate
Latch
Chiller
Immediate
Latch
Chiller
Immediate
Latch
Chiller
Warning
NonLatch
and Special
Action
Circuit
Normal
Latch
Cprsr
Immediate
Latch
Cprsr
Immediate
Latch
Circuit
Warning
Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period. Chiller
shall discontinue use of the External Chilled/Hot Water
Setpoint source and revert to the next higher priority for
setpoint arbitration
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period. Chiller
shall discontinue use of the External Demand Limit Setpoint
source and revert to the next higher priority for setpoint
arbitration
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period. Chiller
shall discontinue use of the Auxiliary Setpoint and revert to the
Chilled Water Setpoint based on setpoint arbitration
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period. Use the
last values sent from BAS
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
CG-SVU02B-E4