Control function

1. Normal PID control
ogy Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE |
Parameter to be used
(Proportional band)
(Integral time)
(Derivative time)
Set the proportional band using the
ratio (%) with respect to the input
full scale (0.0-999.9%).
Setting
to 0.0 provides the 2-
point (ON-OFF) control. The 2-point
control is not available in the fuzzy
control mode. This parameter is
automatically set with auto-tuning.
Set the integral time in sec units (0-
3200 sec).
Setting
to 0 provides no integral
operation.This parameter is
automatically set with auto-tuning.
Set the derivative time in 0.1-sec
units (0.0-999.9 sec).
Setting
to 0.0 provides no
derivative operation. This
parameter is automatically set with
auto-tuning.