Nv/field
Net Data Type
HeatStages
3bits
PeriphHeatOn
Ubit
AuxOn
Ubit
FanOn
Ubit
DlcShed
Ubit
HeatCoolSwitch
Ubit
WindowOpen
Ubit
LowFlowAlarm
Ubit
IaqOvr
Ubit
Free1On
Ubit
MonSwitch
Ubit
SpcTempAlm
Ubit
Future
2bits
nvoCtlDataG2
TempControlPt
SNVT
temp_p
SpaceTemp
SNVT
temp_p
SpaceCO2
SNVT
ppm
SpaceRH
SNVT
lev_cont
DischargeTemp
SNVT
temp_p
SupplyTemp
SNVT
temp_p
FreshAirRatio
SNVT
lev_percent
Table 22. Network Variable - Outputs (Continued)
Heating stages active
0
≤
range
≤
3
Peripheral heat stage 1
0: inactive
1: active
Auxiliary circuit status
0 - effective occupancy is not Occ
1- effective occupancy is Occ
Fan digital output status
0 – off
1 – on
Indicates the status of the Demand limit control load shed.
0 – inactive
1 – active
Heat Cool Change Over Switch
0 – Cool Mode (cool air is supplied to the ZT)
1 – Heat Mode (warm air is supplied to the ZT)
indicates the current state of the window sensors (local input, network input or Share
input)
1 - that the window is open
0 - that the window is closed.
Low airflow alarm
0 – inactive
1 – active
IAQ override alarm. The space CO2 sensor exceeds the high limit.
0 – inactive
1 – active
Free digital output # 1 status. Controlled by network input nviFree1
0 – inactive
1 – active
The state of the digital input wired to a general purpose monitor switch
1 - switch is closed
0 - switch is open
Occupied Space Temperature alarm
0 – inactive
1 – active
Node Status Group – Analog Data
This is a limited summary of VAV analog data intended for Workstation Graphics.
Space temperature effective setpoint
40
≤
range
≤
100F
Space temperature
≤
≤
14
range
122F
Space CO2
≤
≤
0
range
5000 PPM
Invalid = 65535
Space relative humidity
≤
≤
0
range
100%
Invalid = 127.5
Discharge air temperature setpoint
-49
≤
range
≤
233.6 F
Duct in supply air temperature.
≤
≤
32
range
212 F
100 * (FreshAirRequired / BoxFlow)
≤
≤
0
range
150%
79
Description
31-00083—02