Honeywell CVL4022ASVAV1 Engineering Manual page 55

Stryker lon vav system
Table of Contents

Advertisement

NCI/Field
PeriphHtgMin
NCI/Field
Net Data Type
nciAO1
analogRng
nciAO2
analogRng
nciDO1
type
Table 17. Logical Input Configuration (Continued)
Net Data
Default
Type
Val
ubyte
255
Peripheral heating valve minimum position. Typically used to connect an
accessory loop reset schedule.
0
255 Undefined
Table 18. Local Output Configuration
Default Val
ubyte
0
ubyte
0
ubyte
0
range
255
36
nviFree1Mod_levPercentoutSnapshot
47
AccPid1OUTPUTSnapshot
48
AccPid2OUTPUTSnapshot
49
Acc1ResetEFF_OUTPUTSnapshot
50
Acc2ResetEFF_OUTPUTSnapshot
Configure local analog output
Analog range selection
0: 0 to 10 vdc (AO_0_10vdcDir)
1: 10 to 0 vdc (AO_0_10vdcRev)
2: 2 to 10 vdc (AO_2_10vdcDir)
3: 10 to 2 vdc (AO_2_10vdcRev)
4: 0 to 20 mA (AO_0_20maDir)
5: 20 to 0 mA (AO_0_20maRev)
6: 0 to 22 mA (AO_0_22maDir)
7: 22 to 0 mA (AO_0_22maRev)
8: 4 to 20 mA (AO_4_20maDir)
9: 20 to 4 mA (AO_4_20maRev)
10: Binary output (AO_Binary)
Configure local analog output
Analog range selection
0: 0 to 10 vdc (AO_0_10vdcDir)
1: 10 to 0 vdc (AO_0_10vdcRev)
2: 2 to 10 vdc (AO_2_10vdcDir)
3: 10 to 2 vdc (AO_2_10vdcRev)
4: 0 to 20 mA (AO_0_20maDir)
5: 20 to 0 mA (AO_0_20maRev)
6: 0 to 22 mA (AO_0_22maDir)
7: 22 to 0 mA (AO_0_22maRev)
8: 4 to 20 mA (AO_4_20maDir)
9: 20 to 4 mA (AO_4_20maRev)
10: Binary output (AO_Binary)
Configure local digital output
Digital output type
0: Binary output
1: Pulse width modulating output
55
Description
Description
31-00083—02