Honeywell CVL4022ASVAV1 Engineering Manual page 65

Stryker lon vav system
Table of Contents

Advertisement

Net Data
NCI/Field
Type
AuxPlsOff
ubyte
FreeDig1
ubyte
FreePlsOn
ubyte
Table 20. Logical Output Configuration (Continued)
Default
Val
255
Auxiliary pulse OFF output. Typically connected to a lighting relay. The output is
pulsed when the effective occupancy changes not occupied.
Output Type: Binary
Default: Undefined
0
range
255
0
AO1in
1
AO2in
2
DO1in
3
DO2in
4
DO3in
5
DO4in
255 Undefined
255
Free digital output. Controlled from the network command through nviFree1Dig
Output Type: Binary
Default: Undefined
0
range
255
0
AO1in
1
AO2in
2
DO1in
3
DO2in
4
DO3in
5
DO4in
255 Undefined
255
Free digital pulse ON output. Typically connected to a lighting relay. The output
is controlled from the network command through nviFree1Dig.
Output Type: Binary
Default: Undefined
0
range
255
0
AO1in
1
AO2in
2
DO1in
3
DO2in
4
DO3in
5
DO4in
255 Undefined
Description
65
31-00083—02

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cvl4024nsvav1

Table of Contents