Honeywell CVL4022ASVAV1 Engineering Manual page 41

Stryker lon vav system
Table of Contents

Advertisement

NCI/Field
Net Data Type
out4
uint16
out5
uint16
out6
uint16
out7
uint16
out8
uint16
out9
uint16
out10
uint16
out11
uint16
out12
uint16
nciCstmSnsr2
sensorType
ubyte
lowVal
float
highVal
float
toolUnits
ubyte
userUnitLow
float
userUnitHigh
float
nciCstmSnsr2I
in1
uint16
in2
uint16
in3
uint16
in4
uint16
in5
uint16
in6
uint16
in7
uint16
in8
uint16
in9
uint16
in10
uint16
in11
uint16
in12
uint16
nciCstmSnsr2O
out1
uint16
out2
uint16
out3
uint16
out4
uint16
out5
uint16
out6
uint16
out7
uint16
Table 15. Local Input Configuration (Continued)
AP Internal
Default Val
Units
0
0
0
0
0
0
0
0
0
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
41
Description
Custom Sensor #2 Configuration
Sensor type
0: voltage
1: resistive
255: unconfigured
Sensor reference low limit value in output counts. If the
'output count' falls below this value, the controller will report
an INVALID value for the sensor.
Sensor reference high limit value in output counts. If the
'output count' falls above this value, the controller will report
an INVALID value for the sensor.
Tool unit identifier. This is an enumeration identifying the units
associated with the custom sensor analog input. For external
tool use only. It is of no interest to the controller.
Sensor reference low value in user selected engineering units
that corresponds to an output count of 10.
Sensor reference high value in user selected engineering
units that corresponds to an output count of 65510.
Custom Sensor #2 Configuration Input Counts
Data point 1 input counts.
Custom Sensor #2 Configuration Output Counts
Data point 1 output counts.
31-00083—02