Honeywell CVL4022ASVAV1 Engineering Manual page 58

Stryker lon vav system
Table of Contents

Advertisement

NCI/Field
Net Data Type
nciFloat2
action
travelTime
autoSync
syncIntvl
pwrUpSync
pwrUpDelay
UnOccSync
NviSync
31-00083—02
Table 18. Local Output Configuration (Continued)
Default Val
ubyte
0
SNVT_
0
time_sec
ubyte
0
SNVT_
24
time_hour
ubyte
0
SNVT_
0
time_sec
ubyte
0
ubyte
0
Configure floating output
Pin1 = DO1 (DO must be configured binary, nciDO1.type =
0)
Pin2 = DO2 (DO must be configured binary, nciDO2.type =
0)
Note:
To free up binary outputs DO1 & DO2, set the travelTime =
0.
Reverse action
0: False 100%=full open, 0% = full closed
1: True 100%=full closed, 0% = full open
Motor travel time
0 ≤
≤ 3276.7 sec
range
Precision: 1
Notes:
1. Set the travel time to zero to disable the Floating Output
and free up DO1 & DO2
Auto Sync Type
0: none
1: Sync closed
2: Sync open
Refer to Appendix E – Floating Actuator Auto Synch
Auto sync interval
0 ≤
≤ 254 hours
range
Precision: 0
Power up Sync Type
0: none
1: Sync closed
2: Sync open
Refer to Appendix E – Floating Actuator Auto Synch
Actuator Power up delay.
0 ≤
≤ 3276.7 sec
range
Precision: 1
Sync the floating actuator on an occupancy transition to
unoccupied.
0: none
1: Sync closed
2: Sync open
Sync the floating actuator on an active nviFree1Dig signal.
0: none
1: Sync closed
2: Sync open
58
Description