NCI/Field
WallModOvrdBut
31-00083—02
Table 17. Logical Input Configuration (Continued)
Net Data
Default
Type
Val
ubyte
255
Wall module occupancy override button. Typically used with the
conventional wall module. Must be connected to UI1 on Spyder Micro
hardware.
Application Units: Binary Value
0
255 Undefined
Notes:
If 4 (DI_1) is selected, UI_1 is inactive and cannot be assigned to another
logical input.
Override Type = Normal
0.2 to 1.1
second
1.2 to 4
seconds
4.1 to 7
seconds
Longer than
7.1 seconds
Override Type = Bypass Only
0.2 to 1.1
second
1.2 to 4
seconds
4.1 to 7
seconds
Longer than
7.1 seconds
range
255
4
DI_1outLive
Override
Button Held
Down
LED
Override
OFF
OCCNUL No Override (cancel)
ON
BYPASS
1 flash/
UNOCC
sec
OFF
OCCNUL No Override (cancel)
Override
Button Held
Down
LED
Override
OFF
OCCNUL No Override (cancel)
ON
BYPASS
OFF
OCCNUL No Override (cancel)
OFF
OCCNUL No Override (cancel)
54
Description
WM
Comment
Timed Occupied Override
Timer (re)loaded whenever the
button is pressed for this
duration.
WM Override is set to OCCNUL
when timer expires.
Unoccupied Override
WM
Comment
Timed Occupied Override
Timer (re)loaded whenever the
button is pressed for this
duration.
WM Override is set to OCCNUL
when timer expires.