NCI/Field
Net Data Type
pwmPer
pwmZero
pwmFull
nciDO2
type
pwmPer
pwmZero
pwmFull
nciDO3
type
pwmPer
pwmZero
pwmFull
nciDO4
type
pwmPer
pwmZero
pwmFull
31-00083—02
Table 18. Local Output Configuration (Continued)
Default Val
SNVT_
25.6
time_sec
SNVT_
0.1
time_sec
SNVT_
25.5
time_sec
ubyte
0
SNVT_
25.6
time_sec
SNVT_
0.1
time_sec
SNVT_
25.5
time_sec
ubyte
0
SNVT_
25.6
time_sec
SNVT_
0.1
time_sec
SNVT_
25.5
time_sec
ubyte
0
SNVT_
25.6
time_sec
SNVT_
0.1
time_sec
SNVT_
25.5
time_sec
PWM period in seconds
1 ≤
≤ 3276.7 sec
range
Precision: 1 (data entry in seconds)
PWM zero time in seconds
1 ≤
≤ 3276.7 sec
range
Precision: 1 (data entry in seconds)
PWM full time in seconds
1 ≤
≤ 3276.7 sec
range
Precision: 1 (data entry in seconds)
Configure local digital output
Digital output type
0: Binary output
1: Pulse width modulating output
PWM period in seconds
1 ≤
≤ 3276.7 sec
range
PWM zero time in tenths of seconds
1 ≤
≤ 3276.7 sec
range
PWM full time in seconds
1 ≤
≤ 3276.7 sec
range
Configure local digital output
Digital output type
0: Binary output
1: Pulse width modulating output
PWM period in tenths of seconds
1 ≤
≤ 3276.7 sec
range
PWM zero time in seconds
1 ≤
≤ 3276.7 sec
range
PWM full time in seconds
1 ≤
≤ 3276.7 sec
range
Configure local digital output
Digital output type
0: Binary output
1: Pulse width modulating output
PWM period in seconds
1 ≤
≤ 3276.7 sec
range
PWM zero time in seconds
1 ≤
≤ 3276.7 sec
range
PWM full time in seconds
1 ≤
≤ 3276.7 sec
range
Precision: 0
56
Description