Commands To The Drive Converter (Binary Value Processing) - Siemens SIMOVERT MV Series Commissioning Instructions

Medium-voltage converters with hv-igbt and ihv filter
Table of Contents

Advertisement

5.2.3

Commands to the drive converter (binary value processing)

Keys B1 to B4 can always be selected, with the exception when system processing
%
has been selected (SYSTEM).
.
The LED on the four binary keys indicates whether the appropriate binary value is
.
.
at "0" (LED dark) or at "1" (LED bright). The status is inverted by pressing the key.
%
The LED flashes each time the key is pressed, until SIMADYN D acknowledges
the change.
If the binary values are not configured on the SIMADYN D side, then the
LEDs of keys B1to B4 remain dark (this means that the keys have no effect).
Start of the binary value menu. Binary values B5 to B32 are processed.
%,1
The binary values cannot be saved in the EPROM of SIMADYN D. If this is
and
required, the binary values must be configured as process data in SIMADYN D.
or
The actual function is exited using:
The software supports the command keys B3 and B4 and the binary values B5 to
B9.
The command key B3 [LT] initiates the lamp test for the signal lamps in the front
panel of the drive converter.
The command key B4 [Acknowledge] is used to acknowledge drive converter
faults. The acknowledge signal is generated at each edge change.
This manually triggers the trace blocks. The trace is stopped using this command.
Actual values, saved in the ring buffer, can be read-out. The trace recording is also
stopped by a class 1 error, class 2 error, or a threshold comparison.
For the threshold comparison, a selected actual value is compared with a freely
selectable threshold.
The trigger conditions > = < are possible.
Trace record enable. The trace record is enabled using this command. The actual
values are cyclically written into the ring buffer.
Trace output. The values saved in the ring buffer are output using this command. If
the command is repeated, the output is repeated. This command does not delete
the ring buffer.
This deletes the ring buffer trace. This command deletes the values saved in the
ring buffer.
When the drive converter is in the OFF condition, the fan or the cooling unit can be
powered-up with binary value 9 from the OP2 operator control device.
Siemens AG
6SE8004-0BH76
SIMOVERT MV
Commissioning Instructions