Note
After changing the hardware configuration, download takes place practically automatically.
You then no longer have to perform the steps described in sections Step 2: Stopping the
reserve CPU (Page 157) to Step 5: Transition to redundant system mode (Page 159). The
system behavior remains as described.
You will find more information in the HW Config online help "Download to module ->
Download station configuration in RUN mode". You will find more information in the HW
Config online help "Download to module -> Download station configuration in RUN mode".
10.5.2

Step 1: Editing CPU parameters offline

Starting situation
The fault-tolerant system is operating in redundant system mode.
Procedure
1. Edit the relevant CPU properties offline in HW Config.
2. Compile the new hardware configuration, but do not load it into the target system just yet.
Result
The modified hardware configuration is in the PG/ES. The target system continues operation
with the old configuration in redundant system mode.
10.5.3

Step 2: Stopping the reserve CPU

Starting situation
The fault-tolerant system is operating in redundant system mode.
Procedure
1. For CPU access protection with password: In SIMATIC Manager, select a CPU of the
2. In SIMATIC Manager, select a CPU of the fault-tolerant system, then select "PLC >
3. In the "Operating Mode" dialog box, select the standby CPU and click "Stop".
CPU 410-5H Process Automation/CPU 410 SMART
System Manual, 10/2013, A5E32631667-AA
fault-tolerant system, then select
"PLC > Access Rights > Setup" from the menu. Enter the CPU access password.
Operating Mode" from the menu.
System modifications during redundant operation
10.5 Editing CPU parameters
157