Configuring Mode oFPA (Offline Parameters)

In the oFPA configuring mode the parameters are arranged whose effect on the process does
not need to be monitored when they are adjusted. The other parameters are arranged in the
parameterization mode onPA and in the configuring mode CLPA. The offline parameters are
listed in table 3-4. The parameters against a white background (signal range or display range of
the displays dA1 and dd1 to dd3 are always accessible).
The parameters against a gray background are the private parameters of the complex functions
and the signal range of the analog display dA2 as well as the private parameters of the SES.
They only appear if the complex functions are defined in FdEF and selected in hdEF dA2 or the
SES was answered with YES.
Parameter
value
Striped pattern
ID offline
dA1
Dark for switch-
able parameters,
Name of the function for
private parameters
Parameter name
dA ... Cbt
Adjustment of parameter name and function name;
Figure 3-8
Control and display elements in the configuring mode oFPA
SIPART DR24 6DR2410
C79000-G7476-C153-03
dd1
L1
L2
L3
L4
L5
L6
dA2/
L14
L7
L8
L9
L10
L11
dd2
L13
tA7
dd3
L12
Switching: SEt ↔ roLL
3.3 Configuring Mode (Parameterization and Configuring Mode)
3.3.3 Configuring Mode oFPA (Offline Parameters)
tA1
Exit key↗: return to configuring
Exit LED:
tA2
Adjustment of parameter value with fast action
at SEt without function in roLL
tA3
tA4
Enter key:
Enter LED:
tA5
All unnamed keys have no function, all unnamed
LEDs and displays are dark
tA6
3 Operation
pre--selection level after oFPA
flashes
no function
off