11.6.9 Step 9, Change The Parameters To The "Reset" Function - Siemens XC1003-A Technical Manual

Extinguishing control unit
Table of Contents

Advertisement

Programming the user functions

11.6.9 Step 9, change the parameters to the "Reset" function

Change the reaction after "Reset" of the detector zones 1 and 2
Select
Option
Function
KEY13
1 (default)
Alarm <15 seconds after "Reset" = New line alarm
2
Alarm <15 seconds after "Reset" = Line fault
Change the reaction after "Reset" of the detector zone 3
Select
Option
Function
KEY13
3 (default)
Alarm <15 seconds after "Reset" = New line alarm
4
Alarm <15 seconds after "Reset" = Line fault
Change the reaction after "Reset" of the detector zone 4 (manual release)
Select
Option
Function
KEY14
5
Alarm <15 seconds after "Reset" = New line alarm
6 (default)
Alarm <15 seconds after "Reset" = Line fault
Change the reaction after "Reset" of the monitored input 1
Select
Option
Function
KEY15
State "Active 1" <15 seconds after "Reset" = "Released" enabled
7
again (LED8 flashing)
State "Active 1" <15 seconds after "Reset" = "Released" not enabled
8 (default)
(LED8 in steady mode + "Fault")
"Active 1" = 680
Interlock the "Reset" function if executed via control input 1
Select
Option
Function
KEY16
9
Reset always possible
In case of "Fire alarm": Reset possible only after "Silence buzzer"
10 (default)
In case of "Activated" and "Released": Reset possible only after
"Silence horn" and after the flooding time of control line 4 has elapsed
Interlock the "Reset" function
Select
Option
Function
KEY16
11 (default) Reset always possible
Reset not possible if:
zone 4 is on state "Alarm"
12
monitored input 1 is on state "Active 1"
control line 1 (horn) is in state "Active"
"Active 1" = 680
84
Building Technologies
Fire Safety & Security Products
Zone 1
Zone 2
Zone 3
Red
Yel. Red Yel. Red Yel. Red Yel.
Zone 1
Zone 2
Zone 3
Red
Yel.
Red Yel. Red Yel. Red Yel.
Zone 1
Zone 2
Zone 3
Red Yel.
Red
Yel. Red Yel. Red Yel.
Zone 1
Zone 2
Zone 3
Red Yel. Red Yel.
Red
Yel. Red Yel.
Zone 1
Zone 2
Zone 3
Red Yel. Red Yel. Red Yel.
Zone 1
Zone 2
Zone 3
Red Yel. Red Yel. Red Yel. Red
A6V10099837_a_en
Zone 4
Zone 4
Zone 4
Zone 4
Zone 4
Red
Yel.
Zone 4
Yel.
12.2007

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents