Connection examples for redundant I/Os
C.2 Interconnection of output modules
Information on connecting digital output modules via diodes
● Suitable diodes are diodes with U
1N4003 ... 1N4007).
● It is advisable to separate the ground of the module and the ground of the load. There
must be equipotential bonding between both.
Information on connecting analog output modules via diodes
● Suitable diodes are diodes with U
1N4003 ... 1N4007).
● A separate load supply is advisable. There must be equipotential bonding between both
load supplies.
308
>=200 V and I_
>= 1 A (e.g., types from the series
_r
F
>=200 V and I_
>= 1 A (e.g., types from the series
_r
F
CPU 410-5H Process Automation/CPU 410 SMART
System Manual, 10/2013, A5E32631667-AA