Supplementary information
16.15 Cycle and response times of the CPU 410-5H
Extending the cycle time
The calculated cycle time of a S7-400H CPU must be multiplied by a CPU-specific factor.
The table below lists these factors:
Table 16- 12 Extending the cycle time
Startup
Factor
Long synchronization cables may increase cycle times. This extension can have the factor 2
- 5 with a cable length of 10 km.
Operating system execution time at the cycle control point
The table below shows the operating system execution time at the cycle checkpoint of the
CPUs.
Table 16- 13 Operating system execution time at the cycle control point
Sequence
Cycle control at the SCCP
Extended cycle time due to nested interrupts
Table 16- 14 Extended cycle time due to nested interrupts
CPU
Hardware
interrupt
CPU 410-5H
75 µs
stand-alone
mode
CPU 410-5H
180 µs
redundant
The program runtime at interrupt level must be added to this time extension.
If several interrupts are nested, their times must be added together.
276
CPU 410-5H stand-alone mode
1.05
CPU 410-5H stand-alone mode
25 - 330 µs
∅ 30 µs
Diagnostic
Time-of-
interrupt
day
interrupt
40 µs
50 µs
70 µs
200 µs
Delay interrupt
Cyclic
interrupt
40 µs
40 µs
120 µs
120 µs
CPU 410-5H Process Automation/CPU 410 SMART
CPU 410-5H redundant
1.2
CPU 410-5H redundant
120 - 600 µs
∅ 135 µs
Programming
I/O
error
access
error
20 µs
20 µs
90 µs
45 µs
System Manual, 10/2013, A5E32631667-AA
Asynchro-
nous
error
55 µs
130 µs