Technical data
14.1 Technical specifications of the CPU 410-5H; (6ES7 410-5HX08-0AB0)
Local port numbers used by the system
Keep Alive function supported
3. Interface
Type of interface
Physics
4. Interface
Type of interface
Plug-in interface modules
5. Interface
Type of interface
Plug-in interface modules
Protocols
PROFINET IO
PROFINET CBA
PROFIsafe
PROFIBUS
Protocols (Ethernet)
TCP/IP
Other protocols
AS-i
MODBUS
Foundation Fieldbus
Communication functions
PG/OP communication
Number of connectable OPs without message processing 119
Number of connectable OPs with message processing
Data record routing
S7 routing
S7 communication
Supported
As server
As client
User data per job, max.
User data per job (consistent), max.
Open IE communication
TCP/IP
Number of connections, max.
Data length, max.
Several passive connections per port, supported
200
6ES7410-5HX08-0AB0
0, 20, 21, 25, 102, 135, 161, 34962, 34963, 34964, 65532,
65533, 65534, 65535
Yes
integrated
RJ45 (only for service)
Plug-in synchronization module (FOC)
Synchronization module 6ES7960-1AA06-0XA0 or
6ES7960-1AB06-0XA0
Plug-in synchronization module (FOC)
Synchronization module 6ES7960-1AA06-0XA0 or
6ES7960-1AB06-0XA0
Yes
No
Yes
Yes
Yes
Yes; via add-on
Yes; via add-on
Yes; via DP/FF link
Yes
119; when using Alarm_S/SQ and Alarm_D/DQ
Yes
Yes
Yes
Yes
Yes
64 KB
462 bytes; 1 variable
Yes; via integrated PROFINET interface and loadable FBs
118
32 KB
Yes
CPU 410-5H Process Automation/CPU 410 SMART