Structure of the CPU 410-5H
3.2 Monitoring functions of the CPU 410-5H
Type of error
Program execution error
Failure of a rack/station
Communication error
Execution canceled
Missing license for Runtime
software
Programming error
MC7 code error
36
Cause of error
Priority class is called, but the corresponding OB is not
available.
In the case of an SFB call: Missing or faulty instance DB
Process image update error
Power failure in an S7-400 expansion unit
Failure of a DP/PN segment
Failure of a coupling segment: Missing or defective IM,
interrupted cable
Communication error:
Time synchronization
Access to DB when exchanging data via communications
function blocks
The execution of a program block was canceled. Possible reasons
for the cancellation are:
Nesting depth of nesting levels too great
Nesting depth of master control relay too great
Nesting depth of synchronization errors too great
Nesting depth of block call commands (U stack) too great
Nesting depth of block call commands (B stack) too great
Error during allocation of local data
Internal error due to missing licenses for Runtime software.
User program error:
BCD conversion error
Range length error
Range error
Alignment error
Write error
Timer number error
Counter number error
Block number error
Block not loaded
Error in the compiled user program, for example, illegal OP code or
a jump beyond block end
Error LED
INTF
EXTF
EXTF
BUSF for PN and DP
REDF for redundant
segments
INTF
INTF
INTF
INTF
INTF
CPU 410-5H Process Automation/CPU 410 SMART
System Manual, 10/2013, A5E32631667-AA