Technical specifications
6.1 Technical specifications
Article number
Diagnostic messages
Wire-break
•
Short-circuit
•
Group error
•
Overflow/underflow
•
Diagnostics indication LED
Monitoring of the supply voltage (PWR-
•
LED)
Channel status display
•
for channel diagnostics
•
for module diagnostics
•
Potential separation
Potential separation channels
between the channels
•
between the channels and backplane bus
•
between the channels and the power supp-
•
ly of the electronics
Permissible potential difference
between the inputs (UCM)
Isolation
Isolation tested with
Dimensions
Width
Height
Depth
Weights
Weight, approx.
Dimension drawing
See manual ET 200SP BaseUnits
(http://support.automation.siemens.com/WW/view/en/59753521)
36
6ES7134-6HB00-0DA1
Yes; channel-by-channel, at 4 to 20 mA only
Yes; channel-by-channel, at 1 to 5 V or for cur-
rent measuring ranges short-circuit in encoder
supply
Yes
Yes
Yes; green PWR LED
Yes; Green LED
Yes; Red LED
Yes; green/red DIAG LED
Yes
Yes
Yes
75 V DC/60 V AC
707 V DC (type test)
15 mm
73 mm
58 mm
32 g
Analog input module AI 2xU/I 2-/4-wire HS (6ES7134-6HB00-0DA1)
Manual, 09/2018, A5E03576060-AF