Article number
Supply voltage
Rated value (DC)
permissible range, lower limit (DC)
permissible range, upper limit (DC)
Reverse polarity protection
Input current
Current consumption (rated value)
24 V encoder supply
24 V
•
Short-circuit protection
•
Output current, max.
•
Power loss
Power loss, typ.
Address area
Address space per module
Address space per module, max.
•
Hardware configuration
Selection of BaseUnit for connection variants
2-wire connection
•
4-wire connection
•
Analog inputs
Number of analog inputs
For current measurement
•
For voltage measurement
•
permissible input voltage for voltage input
(destruction limit), max.
permissible input current for current input (de-
struction limit), max.
Cycle time (all channels), min.
Analog input with oversampling
Values per cycle, max.
•
Resolution, min.
•
Analog input module AI 2xU/I 2-/4-wire HS (6ES7134-6HB00-0DA1)
Manual, 09/2018, A5E03576060-AF
6ES7134-6HB00-0DA1
24 V
19.2 V
28.8 V
Yes
39 mA; without sensor supply
Yes; For current measurement
Yes
20 mA; max. 50 mA per channel for a duration <
10 s
0.95 W; without sensor supply
4 byte; + 1 byte for QI information (32 bytes in the
oversampling operating mode)
BU type A0, A1
BU type A0, A1
2; Differential inputs
2
2
30 V
50 mA
125 µs
Yes
16
50 µs
Technical specifications
6.1 Technical specifications
33