SETPOINT Menu
Low Ambient Comp Lockout Temp:
Comp(s) OFF if OA Temp Below This Value
1.
Press the NEXT key until the following screen is displayed.
Setpoint Source Selections Submenu
Press ENTER to Review or Adjust
1.
Press the NEXT key until the following screen is displayed.
For Supply Air Temp Cooling Control,
Setpoint From: HI (KEYPAD) SETPOINT MENU
1.
Press the NEXT key until the following screen is displayed.
For Supply Air Temp Heating Control,
SETPOINT From: HI (KEYPAD) SETPOINT MENU
1.
Press the NEXT key until the following screen is displayed.
For Occ Zone Temp Cooling Control, Use
SETPOINT From: HI (KEYPAD) SETPOINT MENU
1.
Press the NEXT key until the following screen is displayed.
For Occ Zone Temp Heating Control, Use
SETPOINT From: HI (KEYPAD) SETPOINT MENU
1.
Press the NEXT key until the following screen is displayed.
For Unocc Zone Temp Cooling Control, Use
Setpoint From: HI (KEYPAD) SETPOINT MENU
1.
Press the NEXT key until the following screen is displayed.
For Unocc Zone Temp Heating Control, Use
Setpoint From: HI (KEYPAD) SETPOINT MENU
1.
Press the NEXT key until the following screen is displayed.
For Morning Warmup Temp Control, Use
Setpoint From: HI (KEYPAD) SETPOINT MENU
1.
Press the NEXT key until the following screen is displayed.
38
50 F
Use
Use
Used With: All Units
Factory Presets: 50 F
Possible Values: -20 F to 80 F
Used With: All Units
Used With: All Units
Factory Presets: HI (Keypad) Setpoint Menu
Possible Values: HI (KEYPAD) SETPOINT
MENU, ZONE SENSOR SETPOINT MENU, NSB
PANEL SETPOINT INPUT, GBAS 0-5 VDC
MODULE
Used With: All Units when hydronic or electric
heat is installed.
Factory Presets: HI (Keypad) Setpoint Menu
Possible Values: HI (KEYPAD) SETPOINT
MENU, GBAS 0-5VDC Module
Used With: All Units
Factory Presets: HI (KEYPAD) SETPOINT
MENU
Possible Values: HI (KEYPAD) SETPOINT
MENU, ZONE SENSOR SETPOINT INPUT, NSB
PANEL SETPOINT INPUT, GBAS 0-5 VDC
MODULE
Used With: All Units with hydronic or electric
heat.
Factory Presets: HI (KEYPAD) SETPOINT
MENU
Possible Values: HI (KEYPAD) SETPOINT
MENU, ZONE SENSOR SETPOINT INPUT, NSB
PANEL SETPOINT INPUT, GBAS 0-5 VDC
MODULE
Used With: All Units
Factory Presets: HI (KEYPAD) SETPOINT
MENU
Possible Values: HI (KEYPAD) SETPOINT
MENU, ZONE SENSOR SETPOINT INPUT, NSB
PANEL SETPOINT INPUT, GBAS 0-5 VDC
MODULE
Used With: All Units when External, Electric or
Hydronic Heat is installed
Factory Presets: HI (KEYPAD) SETPOINT
MENU
Possible Values: HI (KEYPAD) SETPOINT
MENU, ZONE SENSOR SETPOINT INPUT, NSB
PANEL SETPOINT INPUT, GBAS 0-5 VDC
MODULE, GBAS 0-10VDC Module
Used With: All Units when Electric, External or
Hydronic Heat is installed
Factory Presets: HI (KEYPAD) SETPOINT
MENU
Possible Values: HI (KEYPAD) SETPOINT
MENU, NSB PANEL SETPOINT INPUT
GBAS 0-5VDC Module
PKG-SVP01E-EN