SERVICE MODE Menu
Condenser Fan Speed
Ckt 1 0 %
1.
Press the NEXT key until the following screen is displayed
Condenser Fan Speed
Ckt1 0%
1.
Press the NEXT key to advance the cursor.
2.
Press the NEXT key until the following screen is displayed
Compressor Relays:
K11 OFF
K3 OFf
1.
Press the NEXT key to advance the cursor.
2.
Press the NEXT key until the following screen is displayed
Hydronic Heat
Actuator
0 %
1.
Press the NEXT key until the following screen is displayed.
Heat Stages
Stage OFF
1.
Press the NEXT key until the following screen is displayed.
Note: Only single stage electric heat is available factory installed.
OA Damper Pos
0%
1.
Press the NEXT key until the following screen is displayed.
Supply Fan Bypass Relay
1.
Press the NEXT key until the following screen is displayed.
Ventilation Override Module Output Relay
OFF
1.
Press the NEXT key until the following screen is displayed.
OA Preheater State
1.Press the NEXT key to advance the cursor to the next field within this screen.
2.
Press the NEXT key until the following screen is displayed.
GBAS 0-5 VDC Module Relay Outputs
#1 OFF
#2 OFF
#3 OFF
1.
Press the NEXT key until the following screen is displayed.
Status/Annunc Test
Heat: OFF
Cool: OFF
1.
Press the NEXT key to advance the cursor to the next field within this screen.
2.
Press the NEXT key until the following screen is displayed.
Start Test In
Press TEST START To Begin, STOP To Halt
1.
Press the NEXT key to advance the cursor to the next field within this screen.
2.
Press the NEXT key until the following screen is displayed.
44
Ckt2 0%
K12 OFF
K4 OFF
NORMAL
OFF
#4 OFF
#5 OFF
Sys On (Blinking)
Service: OFF
5 Seconds
Used With: Air-cooled units.
Factory Presets: 0%
Possible Values: AUTO, 0-100%
Used With: Air-cooled units.
Factory Presets: 0%
Possible Values: AUTO, 0-100%
Factory Presets: Off
Possible Values: On, Off
Used With: Units when Hydronic heat is installed.
Factory Presets: 0%
Possible Values: 0 - 100%, AUTO
Used With: All Units when electric Heat is installed
Factory Presets: OFF
Possible Values: OFF, ON
Used With: All units with an airside economizer.
Factory Presets: OA Damper = 0%
Possible Values: OA Damper: 0 to 100%
Used With: Units with VFD and bypass.
Possible Values: Normal, Bypass
Used With: All Units when VOM is installed
Factory Presets: OFF
Possible Values: ON, OFF
Used With: All Units when VCM is installed
Factory Presets: OFF
Possible Values: ON, OFF
Used With: All Units when GBAS is installed
Factory Presets: OFF
Possible Values: 1, 2, 3, 4, 5 = ON, OFF
Used With: All Units
Factory Presets: OFF
Possible Values: HEAT = ON, OFF, COOL = ON,
OFF, SERVICE = ON, OFF
PKG-SVP01E-EN