Siemens SINAMICS S120 Equipment Manual page 71

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

TT system
In a TT system, a point of the generator or the transformer is grounded, normally the neutral
point. The housing of the consumer is connected with the ground using a separate cable.
Figure 4-17
● Power Modules without a line filter can be operated on all TT systems.
● Power Modules with an integrated or external line filter can be operated only in TT
systems with a grounded neutral point.
IT system
In an IT system, the voltage network is either not connected with ground or connected only
using a high-resistance impedance. The housing of the consumer is connected with the
ground using a separate cable.
Figure 4-18
● Power Modules without a line filter can be operated in all IT systems.
● Power Modules with an integrated or external line filter cannot be operated in IT systems.
AC Drive
Manual, 06/2019, 6SL3097-5AL00-0BP1
TT system
IT system
Mains connection and line-side power components
4.8 Line connection variants
69

Advertisement

Table of Contents
loading

Table of Contents