Technical data of the PM240-2, FSE (200 V)
Line voltage 3 AC 200 ... 240 V ±10 %
Article No.
without integrated line filter
Output current
Rated current I
1)
n
Base load current I
H
for S6 duty (40 %) l
S6
Peak current l
max
Type rating
2)
based on I
/ based on I
n
H
Rated pulse frequency
Max. pulse frequency
Power loss
Cooling air requirement
Sound pressure level LpA (1 m)
24 V DC supply
for the Control Unit
Rated input current
Resistance value of the external braking
resistor
Max. cable length
to braking resistor
Line connection L1, L2,
Motor connection U2, V2, W2,
DC link connection DCP, DCN
Connection for braking resistor R1, R2
Max. motor cable length
no EMC Category:
shielded / unshielded
EMC Category C2: shielded
Weight
Rated current I
covers the load cycle for Low Overload.
1)
n
Rated power of a typical standard induction motor at 230 V 3 AC
2)
The values depend on the ambient temperature and the utilization level.
3)
Power loss in the control cabinet: 0.19 kW. The remaining power loss is dissipated through the heat sink.
4)
122
6SL3210-
1PC31-3UL0
A
130
A
104
A
156
A
208
kW
37 / 30
kHz
4
kHz
8
kW
1.38
l/s
153
dB
56 ... 68
3)
A
1.0
A
126
Ω
≥ 2.5
m
15
M10 studs
Torx M8
Conductor cross-section: 35 ... 2 x 120 mm
Tightening torque: 22 ... 25 Nm (210 lbf in)
Screw-type terminal
Torx M5
Conductor cross section: 25 ... 70 mm
Tightening torque: 8 ... 10 Nm (88.5 lbf in)
m
300 / 450
m
150
kg
57
Internal
6SL3210-
6SL3210-
1PC31-6UL0
1PC31-8UL0
154
178
130
154
184
213
260
308
45 / 37
55 / 45
4
4
8
8
1.72
2.09
153
153
56 ... 68
56 ... 68
1.0
1.0
149
172
≥ 2.5
≥ 2.5
15
15
2
(AWG 6 ... 3/0)
2
57
57
Manual, 06/2019, 6SL3097-5AL00-0BP1
Push-through
6SL3211-
1PC31-8UL0
178
154
213
308
55 / 45
4
8
2.09
4)
153
56 ... 68
1.0
172
≥ 2.5
15
(AWG 1 ... 2 x 4/0)