Motor-side power components
7.2 Chassis
NOTICE
Damage to the dV/dt filter by exceeding the maximum output frequency
The maximum permissible output frequency when using a du/dt filter is 150 Hz. The du/dt
filter can be damaged if the output frequency is exceeded.
• Operate the du/dt filter with a maximum output frequency of 150 Hz.
NOTICE
Damage to the dV/dt filter by exceeding the maximum pulse frequency
The maximum permissible pulse frequency when using a du/dt filter is 4 kHz. The du/dt
filter can be damaged if the pulse frequency is exceeded.
• When using the du/dt filter, operate the Motor Module with a maximum pulse frequency
NOTICE
Damage to the dv/dt filter if it is not activated during commissioning
The du/dt filter may be damaged if it is not activated during commissioning.
• Activate the du/dt filter during commissioning using parameter p0230 = 2.
NOTICE
Damage to the dV/dt filter if motor is not connected
du/dt filters which are operated without a motor being connected can be damaged or
destroyed.
• Never operate a du/dt filter connected to the Motor Module without a connected motor.
Note
Cable lengths
Keep the connecting cables to the Motor Module as short as possible (max. 5 m).
208
of 4 kHz.
Manual, 06/2019, 6SL3097-5AL00-0BP1