Component Tests 8 and 9
TM077: 325 & 410 Series II Heat Pump Service Instructions
Rev 00: Issued April 2014
This document is stored and maintained electronically by
Test 8
Fit gauges to the discharge (high)
side access valve and observe the
discharge pressure.
Typical discharge pressure range is
600 – 2100kPa depending on the
storage tank water temperature.
A discharge pressure in excess of
2100kPa may indicate a low water
flow
rate
1800 kPa
refrigerant.
Note: Refer to the Refrigerant Charge
section
on
information on refrigerant charge and
refrigerant charge fault indications.
Test 9
Remove the insulation and hold the
TX valve bulb tightly by hand, to
increase the heat detected. The TX
valve should open with the following
results:
1. Suction
cooler.
2. Evaporator
should increase.
Remove
insulation. The TX valve should now
close, resulting in the reversal of the
above results.
Service. All printed copies are deemed uncontrolled.