ACKAGE NITS FORM NO. P11-763 REV. 1 Supersedes Form No. P11-763 RJNA- HIGH EFFICIENCY SERIES NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] *Unit shown with optional louver panels installed. ISO 9001:2000 “CERTIFIED UNDER THE A.R.I. CERTIFICATION PROGRAM—A.R.I. STANDARD 240”...
TABLE OF CONTENTS Introduction ...3-4 Model Identification Options...5-6 General Data RJNA- Series ...7-13 General Data Notes ...14 Performance Data RJNA- Series ...15-18 Airflow Performance RJNA- Series ...19-21 Electrical Data RJNA- Series ...22-23 Units with Heater Kits RJNA- Series ...24-30 Dimensional Data ...31-33 Accessories ...34-41 Mechanical Specifications ...42 Typical Wiring ...43-49...
INTRODUCTION These quality features are included in the Rheem Outdoor Package Heat Pumps Control Box Access Compressor Access Blower Access Optional Electric Heater Kit Evaporator Coil/Filter Access...
Page 4
INTRODUCTION INTRODUCTION ENGINEERING FEATURES RJNA- Series Package Heat Pumps 1. All models feature Copeland operation. 2. One-piece top over the indoor section with drip lip, drawn painted base pan, and 1" [25.4 mm] raised flanges for supply/return air connections provides superior water management. 3.
Page 6
OPTIONS—RJNA- SERIES FACTORY INSTALLED OPTION CODES FOR RJNA (3-5 Ton) [10.6-17.6 kW] (A036, A042, A048, A060) Option Code Hail Guard Example: RJNA-A060CK000XXX (where XX is factory installed option) Example: No Options RJNA-A060CK000 Example: No Options with Factory Installed Economizer RJNA-A060CK000AAB Example: Options with Hail Guard, Low Ambient, Time Delay and Freeze Stat with No Factory Installed Economizer RJNA-A060CK000BDA Example: Options same as above with Factory Installed Economizer...
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJNA- Series Cooling Performance Gross Cooling Capacity Btu [kW] EER/SEER Nominal CFM/ARI Rated CFM [L/s] ARI Net Cooling Capacity Btu [kW] Net Sensible Capacity Btu [kW] Net Latent Capacity Btu [kW] Net System Power kW Heating Performance (Heat Pumps) Heating Temp.
Page 8
GENERAL DATA—RJNA- SERIES NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJNA- Series Cooling Performance Gross Cooling Capacity Btu [kW] EER/SEER Nominal CFM/ARI Rated CFM [L/s] ARI Net Cooling Capacity Btu [kW] Net Sensible Capacity Btu [kW] Net Latent Capacity Btu [kW] Net System Power kW Heating Performance (Heat Pumps) Heating Temp.
Page 9
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJNA- Series Cooling Performance Gross Cooling Capacity Btu [kW] EER/SEER Nominal CFM/ARI Rated CFM [L/s] ARI Net Cooling Capacity Btu [kW] Net Sensible Capacity Btu [kW] Net Latent Capacity Btu [kW] Net System Power kW Heating Performance (Heat Pumps) Heating Temp.
Page 10
GENERAL DATA—RJNA- SERIES NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJNA- Series Cooling Performance Gross Cooling Capacity Btu [kW] EER/SEER Nominal CFM/ARI Rated CFM [L/s] ARI Net Cooling Capacity Btu [kW] Net Sensible Capacity Btu [kW] Net Latent Capacity Btu [kW] Net System Power kW Heating Performance (Heat Pumps) Heating Temp.
Page 11
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJNA- Series Cooling Performance Gross Cooling Capacity Btu [kW] EER/SEER Nominal CFM/ARI Rated CFM [L/s] ARI Net Cooling Capacity Btu [kW] Net Sensible Capacity Btu [kW] Net Latent Capacity Btu [kW] Net System Power kW Heating Performance (Heat Pumps) Heating Temp.
Page 12
GENERAL DATA—RJNA- SERIES NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJNA- Series Cooling Performance Gross Cooling Capacity Btu [kW] EER/SEER Nominal CFM/ARI Rated CFM [L/s] ARI Net Cooling Capacity Btu [kW] Net Sensible Capacity Btu [kW] Net Latent Capacity Btu [kW] Net System Power kW Heating Performance (Heat Pumps) Heating Temp.
Page 13
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJNA- Series Cooling Performance Gross Cooling Capacity Btu [kW] EER/SEER Nominal CFM/ARI Rated CFM [L/s] ARI Net Cooling Capacity Btu [kW] Net Sensible Capacity Btu [kW] Net Latent Capacity Btu [kW] Net System Power kW Heating Performance (Heat Pumps) Heating Temp.
Page 14
GENERAL DATA—RJNA- SERIES NOTES: 1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm.
COOLING PERFORMANCE DATA—RJNA-A036 CFM [L/s] 1440 [680] DR ➀ Total BTUH [kW] 46.4 [13.60] Sens BTUH [kW] 27.9 [8.18] [23.9] Power Total BTUH [kW] 45.5 [13.33] Sens BTUH [kW] 27.3 [8.00] [26.7] Power Total BTUH [kW] 44.5 [13.04] Sens BTUH [kW] 26.7 [7.83] [29.4] Power...
Page 16
SYSTEMS PERFORMANCE—RJNA- SERIES COOLING PERFORMANCE DATA—RJNA-A042 CFM [L/s] 1680 [793] DR ➀ Total BTUH [kW] 50.3 [14.74] Sens BTUH [kW] 30.8 [9.03] [23.9] Power Total BTUH [kW] 50.3 [14.74] Sens BTUH [kW] 30.8 [9.03] [26.7] Power Total BTUH [kW] 49.6 [14.54] Sens BTUH [kW] 30.3 [8.88] [29.4]...
Page 17
COOLING PERFORMANCE DATA—RJNA-A048 CFM [L/s] 1920 [906] DR ➀ Total BTUH [kW] 59.9 [17.55] Sens BTUH [kW] 35.6 [10.43] [23.9] Power Total BTUH [kW] 58.7 [17.20] Sens BTUH [kW] 35.1 [10.29] [26.7] Power Total BTUH [kW] 57.4 [16.82] Sens BTUH [kW] 34.6 [10.14] [29.4] Power...
Page 18
SYSTEMS PERFORMANCE—RJNA- SERIES COOLING PERFORMANCE DATA—RJNA-A060 CFM [L/s] 2500 [1180] DR ➀ Total BTUH [kW] 74.9 [21.95] Sens BTUH [kW] 44.2 [12.95] [23.9] Power Total BTUH [kW] 74.4 [21.80] Sens BTUH [kW] 44.3 [12.98] [26.7] Power Total BTUH [kW] 73.3 [21.48] Sens BTUH [kW] 43.8 [12.84] [29.4]...
208/230 208/230 Phase Amps (FLA) Amps (LRA) 10.6 1. Horsepower Per Compressor. 2. Amp Draw Per Motor. Multiply Value By Number of Motors to Determine Total Amps. ELECTRICAL DATA – RJNA SERIES 187-253 414-506 414-506 414-506 187-253 19/19 25/25 25/25...
Page 23
Phase Amps (FLA) Amps (LRA) 10.6 1. Horsepower Per Compressor. 2. Amp Draw Per Motor. Multiply Value By Number of Motors to Determine Total Amps. ELECTRICAL DATA—RJNA- SERIES ELECTRICAL DATA – RJNA SERIES 187-253 414-506 414-506 414-506 187-253 22/22 30/30...
ACCESSORIES—RJNA- SERIES ACCESSORY EQUIPMENT Accessory Description Electric Heater Kits Roofcurb 14" Roofcurb 24" Roofcurb Adapters Economizer with Single Enthalpy ➀ Dual Enthalpy Kit Sensor Power Exhaust Fresh Air Damper Manual Fresh Air Damper Motorized Rectangular to Round 18" Duct Adapters for Concentric Diffuser Concentric Diffuser 18"...
Page 35
(-)PNC, (-)PND, (-)RGH (3.5, 4 TON [12-14 kW]) Field Installed Resistance Heater Kits Electric Heater Kits are designed for field installation using either single-point power wiring or dual circuit wiring. Low voltage plugs are provided to allow for quick connection to the unit. Removing a block-...
Page 36
ACCESSORIES ROOFCURBS (Full Perimeter) Rheem’s new roofcurb design can be utilized on 3 through 5 ton [10.6-17.6 kW] models. Two available heights (14" [356 mm] and 24" [610 mm]) for ALL models. Quick assembly corners for simple and fast assembly.
Page 37
ECONOMIZERS RXRD-KECM3—3-5 Ton [10.6-17.6 kW] Models Single Enthalpy with Barometric Relief RXRX-AV02—Dual Enthalpy Kit 3-5 Ton [10.6-17.6 kW] Models RXRX-AR02—3-5 Ton [10.6-17.6 kW] Models Features Honeywell Controls Available factory installed or field accessory Gear Driven Direct Drive Actuator Fully Modulating (0-100%) Low Leakage Dampers Horizontal or Downflow Applications Slip-In Design for Easy Installations...
Page 38
ACCESSORIES INTEGRAL POWER EXHAUST FOR ECONOMIZER (FIELD INSTALLED ONLY) RXRX-BFF04C—3-5 Ton [10.6-17.6 kW] Models 208-230 V, 1 PH, 60 Hz For RXRD-KECM3 Economizer Downflow or horizontal applications Requires separate power supply with disconnect Adjustable switch on economizer, factory preset to energize power exhaust at 95% outside air position Polarized plug connects power exhaust relay to economizer...
Page 39
ACCESSORIES DUCT ADAPTERS (3 TO 5 TON [10.6 TO 17.6 kW] MODELS) Rectangular to Round Transitions (Downflow) RXMC-CB03 – 18" [457 mm] Round Available in 18 inch round to fit all units. Drops into and secures to RXKG- Series Roofcurbs. For use with Concentric Diffusers.
ACCESSORIES SIDE DISCHARGE CONCENTRIC DIFFUSER RXRN-FA60 (3 to 5 Ton [10.6 to 17.6 kW] Models) For Use With Duct Adapter (RXMC) DIMENSIONAL DATA Model No. " " RXRN-FA60 [1210 mm] [600 mm] [289 mm] ENGINEERING DATA Model No. CFM [L/s] 1000 [472] 1200 [566] 1400 [661]...
Page 41
FLUSH MOUNT CONCENTRIC DIFFUSER RXRN-FA70 (3 to 5 Ton [10.6 to 17.6 kW] Models) For Use With Duct Adapter (RXMC) DIMENSIONAL DATA Model No. " " RXRN-FA70 [1210 mm] [600 mm] ENGINEERING DATA Model No. CFM [L/s] 1000 [472] 1200 [566] 1400 [661] RXRN-FA70 1600 [755]...
Page 42
MECHANICAL SPECIFICATIONS—RJNA- SERIES THERMOSTATS—PACKAGE HEAT PUMPS RECOMMENDED HEAT PUMP THERMOSTATS Manufacturer Honeywell General Electric White-Rodgers Maple Chase Honeywell SAMPLE SPECIFICATIONS Unit shall be completely factory assembled and performance tested to provide the required cooling and heating functions suit- able for outdoor installations. Unit shall be UL/cUL listed and rated in accordance to ARI Standard 210.
Federal, State, Provincial, and Local codes, regulations, and practices. “In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice.” PRINTED IN U.S.A. 8-05 DC Compressor ...Five (5) Years...