Test 6
Disconnect the element wire from
terminal 5 of the thermostat and using
a multimeter set on the resistance
(ohms) scale, measure between the
two element wires.
Normal resistance for the element is:
1.8kW: 29Ω – 35Ω
2.4kW: 22Ω – 26Ω
3.6kW: 15Ω – 17Ω
Test 7
Fit gauges to the suction (low) side
access valve and observe the suction
pressure.
The suction pressure is dependent on
ambient
suction pressure range is typically
between 200 – 600kPa:
200kPa @ 10°C ambient
600kPa @ 45°C ambient
A suction pressure of less than
200kPa may indicate a refrigerant
leak or a malfunctioning TX valve.
Note: Refer to the Refrigerant Charge
section
on
information on refrigerant charge and
refrigerant charge fault indications.