Bit Allocation And Dip Switch Settings - Omron C200HX Operation Manual

Hide thumbs Also See for C200HX:
Table of Contents

Advertisement

Analog Timer Unit Programming

4-13-2 Bit Allocation and DIP Switch Settings

Timer Range Setting
Selecting Internal/External
Timer SV Setting
Refer to the Analog Timer Unit's Operation Manual for details on switching
between internal and external timer SV settings, connecting a variable resistor,
and switch settings.
Timer Start Input
Bits 08 to 11 of n
Completion Flags
Timer Start Input
Time-up Output
Timer interval
The following table shows the use of the word (n) allocated to the Analog Timer
Unit. This word address depends upon the slot in which the Unit is mounted.
Bit
I/O class
00
Output
p
Timer 0 Set Bit
01
Timer 1 Set Bit
02
Timer 2 Set Bit
03
Timer 3 Set Bit
04
Timer 0 Stop Bit
05
Timer 1 Stop Bit
06
Timer 2 Stop Bit
07
Timer 3 Stop Bit
08
Input
p
Timer 0 Completion Flag
09
Timer 1 Completion Flag
10
Timer 2 Completion Flag
11
Timer 3 Completion Flag
12 to 15
---
Not used.
Set the timer range with the upper DIP switch on the front of the Unit. Each tim-
er's range can be set independently.
Range
g
Timer 0
Pin 8
0.1 to 1 s
OFF
1 to 10 s
ON
10 to 60 s
OFF
1 to 10 minutes
ON
Select internal or external setting with the lower DIP switch on the front of the
Unit.
Setting
Timer 0 (pin 4)
Internal
ON
External
OFF
Function
ON when timer is set.
OFF: Enable timer operation
ON S
ON: Stop timer operation
ON when timer has timed out.
---
Timer 1
Pin 7
Pin 6
Pin 5
Pin 4
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
ON
ON
Timer 1 (pin 3)
Timer 2 (pin 2)
ON
ON
OFF
OFF
Section 4-13
Timer Set
Bits
(Bits 00 to
03 of n)
Time-up
Output
Comments
p
i
i
Timer 2
Timer 3
Pin 3
Pin 2
Pin 1
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
ON
ON
ON
Timer 3 (pin 1)
ON
OFF
131