DM (Data Memory) Area
Word(s)
Bit(s)
DM 6556
00 to 07
Baud rate
00: 1.2K, 01: 2.4K, 02: 4.8K, 03: 9.6K, 04: 19.2K
08 to 15
Frame format
00:
01:
02:
03:
04:
05:
06:
07:
08:
09:
10:
11:
DM 6557
00 to 15
Transmission delay
0000 to 9999: BCD in 10-ms units.
DM 6558
00 to 07
Node number (Host Link)
00 to 31 (BCD)
08 to 11
Start code enable (RS-232C)
0: Disable; 1: Set
12 to 15
End code enable (RS-232C)
0: Disable (number of bytes received)
1: Set (specified end code)
2: CR, LF
DM 6559
00 to 07
Start code (RS-232C)
00 to FF (binary)
08 to 15
12 to 15 of DM 6558 set to 0:
Number of bytes received
00: Default setting (256 bytes)
01 to FF: 1 to 255 bytes
12 to 15 of DM 6558 set to 1:
End code (RS-232C)
00 to FF (binary)

3-6-6 Special I/O Unit Area Settings

Setting
Mode
00
C200H-compatible
RAM Mode
01
C200H-compatible
ROM Mode 1
02
DM Linear Mode 1 DM 7000 through DM 7999 are used for the Special I/O Unit Area.
Start
Length
1 bit
7 bits
1 bit
7 bits
1 bit
7 bits
1 bit
7 bits
1 bit
7 bits
1 bit
7 bits
1 bit
8 bits
1 bit
8 bits
1 bit
8 bits
1 bit
8 bits
1 bit
8 bits
1 bit
8 bits
The setting in bits 08 through 15 of DM 6602 determines the size and location of
the Special I/O Unit Area, as shown in the following table.
DM 1000 through DM 2599 are used for the Special I/O Unit Area.
• Data in the Special I/O Unit Area can be read/written.
• The data cannot be converted to ROM.
The contents of DM 7000 through DM 7999 are transferred to DM 1000 through DM 1999
at startup and DM 1000 through DM 1999 are used for the Special I/O Unit Area.
• The UM Area Allocation operation must be performed beforehand.
• The data is compatible with C200H applications that use EEPROM/EPROM.
• ROM conversion is possible indirectly by converting DM 7000 through DM 7999 to ROM.
• The UM Area Allocation operation must be performed beforehand.
• DM 1000 through DM 1999 can be used as regular DM.
• DM 7000 through DM 7999 can be converted to ROM.
Function
Stop
Parity
1 bit
Even
1 bit
Odd
1 bit
None
2 bit
Even
2 bit
Odd
2 bit
None
1 bit
Even
1 bit
Odd
1 bit
None
2 bit
Even
2 bit
Odd
2 bit
None
Function
Section 3-6
Default
1.2 K
1 start bit, 7-bit
data, 1 stop bit,
even parity
0 ms
0
Disabled
Disabled
0000