Board Switch Settings

2-3

Board Switch Settings

Setting
UM Write-protection
Program Transfer at
Startup
Programming Console
Display Language
Peripheral Port
Communications Settings
Reserved for system.
Initial Operation Conditions
Easy Backup Setting
DeviceNet Node Address
DeviceNet Unit Number
DeviceNet
Communications
Parameters

2-3-1 PLC DIP Switch Settings (PC SETTING SW)

36
The following settings must be made on the SYSMAC CS1 Board.
We recommend making these settings before installing the Board in the comput-
er. It may be possible to change the settings after installation, but it will probably
be necessary to open the computer case to access the Board.
If the settings are being changed while the Board is installed in the computer,
turn OFF the computer and all connected peripheral devices before changing
the settings. If any Slaves are connected, turn OFF all of the Slaves' power sup-
plies and communications power supplies.
Switch
PLC DIP switch, pin 1
Enables or disables writing to the user memory area.
PLC DIP switch, pin 2
Specifies whether or not to automatically load the program and
parameter data from the Memory Card when the SYSMAC CS1
Board is started.
PLC DIP switch, pin 3
Keep set to ON for English.
PLC DIP switch, pin 4
Specifies whether or not default communications parameters are
to be used.
PLC DIP switch, pin 5
Keep set to OFF.
PLC DIP switch, pin 6
Specifies whether the PLC will wait (CPU standby) until the
computer completes initialization or start executing the ladder
program without waiting for initialization to be completed.
PLC DIP switch, pins
Sets the type of easy backup operation to be performed.
7 and 8
DeviceNet node
Set the node address of the SYSMAC CS1 Board as a DeviceNet
address switches
Master Unit.
DeviceNet node
Set the unit number of the SYSMAC CS1 Board as a DeviceNet
number switch
Master Unit.
DeviceNet DIP switch
Sets the baud rate and whether to stop or continue operations
after a communications error occurs in DeviceNet
communications.
The PLC DIP Switch determines how the SYSMAC CS1 Board operates as a
PLC. This switch also sets the I/O port address that determines which registers
are used for communications between the Board and the computer. (The default
setting is OFF for all pins.)
Section
Description
(Factory defaults shown in diagram.)