All Object Types Sorted By Object Name - Trane Tracer UC600 Installation Manual

For modular self contained
Table of Contents

Advertisement

O O b b j j e e c c t t a a n n d d D D i i a a g g n n o o s s t t i i c c D D a a t t a a P P o o i i n n t t s s
Table 9. All Object Types Sorted by Object Name
Object
Object Name
Identifi-
er
Active CoolCoil Control
AV133
Sensor
Active CoolCoil Control
BV76
Sensor Failed
Active CoolCoil Control
AV134
Setpoint
Air Filter Differential
AI58
Pressure
BV36
Alarm Reset
Circuit 1 Compressor
AV162
Speed
Compressor 1
Calculated Diff
AV300
Refrigerant Pressure
Compressor 1
Calculated Max Speed
AV301
(Percent)
Compressor 1
Calculated Saturated
AV302
Discharge Temp
Compressor 1
Calculated Saturated
AV303
Suction Temp
Compressor 1
Calculated Speed
AV304
(RPM)
Compressor 1
BV190
Calculated Status
Compressor 1
AV305
Calculated Superheat
Compressor 1 Call
BV191
Compressor 1
BO11
Command
Compressor 1 Cond
BV193
Purge Status
Compressor 1 Cond
BV194
Valve Open
Compressor 1
AO81
Condenser Regulating
Valve
Compressor 1
AI93
Discharge Pressure
Sensor
Compressor 1
Estimated Cond
AV306
Approach Temp
Compressor 1
Estimated Evap
AV307
Approach Temp
Compressor 1 E-Stop
BO109
Shutdown Command
Compressor 1 Failure
BV195
Reset
Compressor 1 High
BI90
Pressure Cutout
Compressor 1 Lockout
BV29
BAS
32
Units of
Minimum
Measure
Maximum
Temperature
-50°C (-58°F) to
(°C or °F)
236°C (482°F)
None
None
Temperature
-50°C (-58°F) to
(°C or °F)
236°C (482°F)
Pressure
-10 to 10 in
in(H2O)
(H2O)
None
None
Percent
-150% to 150%
-500 psi to 500
PSI
psi
Percent
-150% to 150%
Temperature
-50°C (-58°F) to
(°C or °F)
236°C (482°F)
Temperature
-50°C (-58°F) to
(°C or °F)
236°C (482°F)
None
0 - 15000 RPM
None
None
Temperature
-50°C (-58°F) to
(°C or °F)
236°C (482°F)
None
None
None
None
None
None
None
None
0% to 100%
Percent
Open
Pressure
0 to 750 PSI
(PSI)
Temperature
-50°C (-58°F) to
(°C or °F)
236°C (482°F)
Temperature
-50°C (-58°F) to
(°C or °F)
236°C (482°F)
None
None
None
None
None
None
None
None
When the Object
Exists
Active Temperature used for
All Units
controlling the cooling calculation
All Units
Non latching Diagnostic, clears
Active Setpoint used for controlling
All Units
the cooling calculation
Local Air Filter Differentil Pressure
All Units
All Units
Units with variable
Speed Status for the variable speed
speed compressor
(s)
Calculated Differential Pressure
Units with 1
between the Discharge and Suction
Compressor
Units with 1
Calculated Maximum Speed in RPM of
Compressor
the Variable speed Compressor
Calculated Saturated Discharge
Units with 1
Temperature calcualted by the
Compressor
refrigerant temp and pressure.
Units with 1
Calculated Suction Temperature by
Compressor
pressure to temperature conversion.
Calculation of the current speed of the
Units with 1
variable speed compressor, based on
Compressor
Min and Max speed setpoints.
Units with 1
Compressor
Calculated Superheat of the Suction
Units with 1
line by Temperautre and pressure
Compressor
Units with 1
Compressor
Normally Open Contacts Used Only
Units with at least 1
Open = Stop Closed = Run
Compressor
Normally Closed Contacts not used
Units with 1
Compressor
Closed = Purge Active
Units with 1
Compressor
Unit that Circuit 1
Analog Control that regulates water
has a Water
throught the water cooled condenser
Regulating Valve
installed
Units with at least 1
Local Compressor Refrigerant
Compressor
Discharge (High) Pressure Sensor
Units with 1
Calculated Condenser approach
Compressor with
temperature based off Refrigerant PT
Cond Reg Valve
Conversion and water temperature.
Calculated approach temperuatre of
Units with 1
the Evaporator refrigerant temprature
Compressor
and the air temperature.
Normally Open Contacts Used Only
Unit where
Open = Normal Closed = Emergency
compressor 1 is a
VFD Compressor
Normally Closed Contacts not used
Units with 1
Compressor
Normally Closed Input
Units with at least 1
Compressor
Units with at least 1
Compressor
Closed = Locked Out
Description
Open = Normal
Closed = Failure
automatically
Sensor
Open = Normal
Closed = Reset
compressor.
Pressure Sensors
Open = Off
Closed = On
sensors.
Open = Stop
Closed = Run
Open = Inactive
Open = Closed
Closed = Open
of the compressor
Stop
Open = Normal
Closed = Reset
Open = Alarm
Closed = Normal
Open = Available
BAS-SVP042A-EN
Read/
Write
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only