PRESSURE TESTING FIREPLACE GAS
CONNECTIONS
1. Open equipment shutoff valve (see Figure 25,
Page 20).
2. Open main gas valve located on or near gas
meter for natural gas or open propane/LP
supply tank valve.
3. Make sure control knob of fi replace is in the
OFF position.
4. Check all joints from equipment shutoff valve to
gas control valve (see Figures 26 or 27, Page
20). Apply noncorrosive leak detection fl uid to
all joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Light fi replace (see Operation, Page 23). Check
all other internal joints for leaks.
7. Turn off fi replace (see To Turn Off Gas to Ap-
pliance, Page 24).
OPTIONAL WIRELESS HAND-HELD
REMOTE CONTROL ACCESSORIES (MRC
AND TRC)
Installing Receiver
1. Remove screws.
2. Disconnect switch wires from control valve.
3. Remove switch plate (see Figure 28). Discard
switch plate after removing. Save the screws.
4. Place remote receiver unit onto fi replace base.
5. Connect the wire harness from the receiver to the
TH and TH/TP terminals on the valve.
6. For further information see installation instruc-
tions provided with remote control kit.
Screw
Black Wire
Figure 28 - Switch Plate and Wiring Harness
126872-01C
INSTALLATION
Continued
OPTIONAL WALL MOUNTED THERMOSTAT
- GWMT1
WARNING: Read and follow instal-
lation instructions. Installation should
be done by a qualifi ed installer familiar
with low-voltage wiring procedures.
WARNING: Do not connect this ther-
mostat to any electrical source! Electri-
cal shock and/or fi re hazard will occur.
1. Connect one terminal of 25 ft. wire to bottom
contact of switch (see Figure 29).
2. Connect remaining wire terminal to "TH" terminal
on control valve. Make sure that wire terminals
are in the positions on your unit as pictured in
Figure 29. If wires are not "crossed" thermostat
will not work.
Switch on Gas
Fireplace
One Terminal of
25 ft. Wire
Figure 29 - Connecting Wire Terminals
WARNING: Caution: Label all wires
prior to disconnection when servicing con-
trols. Wiring errors can cause improper
and dangerous operation. Verify proper
operation after servicing.
3. Route 25 ft. wire to a convenient location to
mount your thermostat (no outside wall). IM-
PORTANT: Wire may be shortened but must not
Switch
be lengthened.
Plate
Thermostat should be mounted 54" above the
fl oor in a location where there is good air circu-
lation. Avoid heat sources such as lamps, direct
Red Wire
sunlight, fi replace, or heat and air conditioning
ducts.
4. Gently remove thermostat cover from base.
Grasp sides of cover fi rmly and pull to separate
from base.
5. Feed electrical wires through rectangular slots on
each side of base (see Figure 30).
SuperiorFireplaces.us.com
Control
Valve
To Wall Thermostat or
Switch
21