3 Software
System Status Tab
The System Status tab displays actual states and diagnostic information like internal temperature, fan
revolution, battery and power supply status.
A status that requires attention is indicated with a red bar.
Item
Internal Temperature
Fan Revolution
*2
Fan Status
Battery Status
Power Supply
*1.
The Fan Revolution will always show 0 (r/min) / 0 (r/min) for fanless models
Refer to 1-4 Product Configuration on page 1-5 for fan details.
*2.
The Fan Status will always show OK for fanless models
Values are not updated automatically. Select the Update Screen Button to display the latest values.
3-8
The average CPU temperature.
The actual rotation speed for each fan in revolutions per minute (r/min).
*1
First number = rotation speed of fan located closest to Power button.
Second number = rotation speed of fan located closest to battery.
The target speed for the fans is dynamically set based on the CPU temperature. The
target speed is compared with the actual fan speed.
OK indicates both fans are running on the target speed.
Low revolution speed indicates one or both fans do not reach the target speed.
Clean the fans and replace the Fan Unit if the problem persists.
The battery status.
OK indicates the battery is full.
Low indicates the battery voltage is low. Replace the battery.
The power supply status is determined by the UPS and reported to the IPC via the I/O
connector.
NormalPowerSupply indicates the IPC is powered by the 24V power supply.
UPS Power Supply indicates that there is no power from the 24V power supply
and the IPC runs on battery power from the UPS.
Description
IPC Application Controller User's Manual (I632)