Hide thumbs Also See for AC1-152000:
Table of Contents

Advertisement

3
Lift the battery
4
Disconnect the battery from the battery connector
5
Connect the new battery to the battery connector.
6
Place the new battery in the IPC.
Ensure the wires are at the side of the battery and not on top of the battery. If the wires are on
top of the battery this might make closing and opening the cover more difficult.
7
Write the next date of replacement on the label at the inside of the cover.
Additional Information
Refer to 2-8-1 Battery on page 2-16 for lifetime of the battery.
8
Mount the cover.
9
Remove the power connector for at least 3 seconds to reset the battery warning.
10
Power ON the IPC.
11
Check the Date and Time in the operating system.
Correct the Date and Time if this is required.
The battery is replaced and the alarm is reset.
IPC Application Controller User's Manual (I632)
1
from the compartment.
1
2
2
.
7 Maintenance