For IPCs that do not have Windows pre-installed: Download the above mentioned software.
3
Wire the S8BA UPS.
1) Wire the input of the UPS to the output of the Power Supply.
2) Wire the output of the UPS to the power connector of the IPC.
3) Ground the UPS.
4) Connect the Contact port of the S8BA UPS to the I/O port of the IPC with the connection
cable S8BW-02.
Power Supply (S8VK)
AC (L)
AC (N)
4
Power ON the IPC.
5
Configure the UPS.
1) Connect the USB cable supplied with the UPS to the USB connector of the UPS and to the
USB connector of the IPC.
2) Configure the UPS using the UPS Settings Utility.
Refer to UPS Setting Utility Instruction Manual for S8BA/BU-2RWL for details.
3) Remove the USB cable between the UPS and the IPC
6
Configure the IPC to auto-start after power loss within the BIOS settings.
Refer to A-1 BIOS on page A-2 for BIOS details.
7
Create a software program that monitors the UPS Mode Input and initiates Power OFF of the
IPC when the UPS Mode Input becomes active.
If the IPC has a Windows operating system then use the Industrial PC System API to create
the software program.
Refer to NY-series Software Development Kit User's Manual for API details.
8
Install the created software program.
9
Test the created software program and ensure it functions correctly.
10
Simulate a power interruption and confirm a correct shutdown of the IPC.
• Start the IPC
IPC Application Controller User's Manual (I632)
UPS (S8BA)
24 VDC
Input
24 VDC
0 VDC
Output
24 VDC
0 VDC
COM
4
1
BU
6
BS
Contact
5 Installation
IPC Product
6
UPS Mode Input
5
UPS Mode Input
2
Power Status Output
1
Power Status Output
I/O
5-47
5