Adjustment Elements - Siemens FS720 Quick Reference For Components / Pin Assignment

Fire detection system
Table of Contents

Advertisement

LED
Colour
Function
H108
Yellow
IO_FAULT
H109
Yellow
IO_DIR
H110
Yellow
IO_1
H111
Yellow
IO_2
H112
Yellow
IO_3
H113
Yellow
IO_4
LED
Colour
Function
H201
Yellow
C-NET loop 1
(module 2)
8.4

Adjustment elements

Switch
Function
S100
Switchover of the indication for the I/O
LEDs (see also H109)
Building Technologies
Fire Safety & Security Products
Indications of programmable inputs / outputs
Condition
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
C-NET indicators
Condition
Off
1 x flashing
(every 2 s)
2 x flashing quickly
(every 2 s)
1 x flashing
(every 1 s)
1 x flashing (every 1 s)
and
2 x quickly flashing
(every 2 s)
On
Position
Switchover
Periphery board (1-loop) FCI2001-A1
STATUS
Normal operation
I/O error (excess temperature, excess voltage, etc.)
I/O STATUS (push button S100)
I/O DIRECTION (push button S100)
High input (default)
Low input
High input (default)
Low input
High input (default)
Low input
High input (default)
Low input
Meaning
Passive (normal operation)
Failsafe active (communication to PMI
interrupted)
Failsafe active + local alarm
Failsafe active + indication (local alarm)
Failsafe active + local alarm + indication
Startup problems C-NET module 2 (clock)
Meaning
STATUS indication
DIRECTION indication
DIRECTION
INPUT (default)
OUTPUT
INPUT (default)
OUTPUT
INPUT (default)
OUTPUT
INPUT (default)
OUTPUT
43