Indications; Adjustment Elements - Siemens FS720 Quick Reference For Components / Pin Assignment

Fire detection system
Table of Contents

Advertisement

6.2

Indications

LED
Color
Function
H32
Yellow
LINK control indicator
H36
Yellow
Processor status indicator
H37
Red
Processor status indicator
H38
Red
Installation ready for switching off
H39
Red
Processor status indicator
H297
Red
Reserved
6.3

Adjustment elements

Building Technologies
Fire Safety & Security Products
S32: Reset key
Operation
Function
Press briefly
The station is shut down in a controlled manner.
After the station has shut down, the 'Power down ready' LED lights up.
This may take up to 5 minutes!
The station may now be disconnected from the supply.
Press for
Hardware reset
approx. 5 s
The station is shut down immediately and rebooted. This may lead to data
loss.
S33: Switch for the ground fault monitoring of the Ethernet
connection
S33-1
S33-2
Function
ON
ON
Ground fault monitoring switched on
OFF
OFF
Ground fault monitoring switched off
OFF
ON
Not admissible
ON
OFF
Not admissible
Note:
The two switches must always be in the same position!
Condition
Meaning
Off
No Ethernet connection
On
Ethernet connection established
Off
Processor in normal operation
On
Processor in degraded mode; replace
component or contact hotline
Off
Processor in normal operation
On
Processor in degraded mode
Off
Installation in operation
On
Installation may be disconnected from the
mains
Off
Processor in normal operation
On
Processor in degraded mode; replace
component or contact hotline
Operator unit FCMxxxx
29
A6V10210410_a_en_--
18.05.2009