7.3

Indications

LED
Color
Function
H101 ...
Red
Power Down Ready
H103
H201
Yellow
Supply output 1
H202
Yellow
Supply output 2
H203
Yellow
Surveillance of the voltage at the supply
input 2 'VSYS2' *
H204
Yellow
Surveillance of the voltage at the supply
input 1 'VSYS1' *
H207
Yellow
Power supply surveillance
'CONVERT_DEF_IN'
H206
Yellow
Mains voltage surveillance
'MAINS_FAIL_IN'
H205
Green
Battery surveillance
'BATT_DEF_IN'
Building Technologies
Fire Safety & Security Products
X7, supply input 1
PIN
Designation
4
VSYS - 1
3
VSYS - 1
2
VSYS + 1
1
VSYS + 1
Admissible cable cross-section: 0,2 ... 2,5 mm²
X7
VSYS -1
4
-
3
VSYS -1
-
+
VSYS +1
2
+
VSYS +1
1
* For a correct indication the switch S1 must be in the corresponding position!
Fire terminal board FTI2001-A1
Description
Ground
Ground
System supply 21 ... 28.6 V DC (+)
System supply 21 ... 28.6 V DC (+)
Conditio
Meaning
n
Off
Normal operation
On
Control panel may be disconnected from the
mains
Off
Fuse ok
On
Fuse damaged
Off
Fuse ok
On
Fuse damaged
Off
Supply available
On
No supply and surveillance is switched on
(S1-1 = ON)
Off
Supply available
On
No supply and surveillance is switched on
(S1-2 = ON)
On
Fault in the power supply unit
Off
Normal condition
On
No mains voltage
Off
Normal condition
On
Battery fault
Off
Normal condition