Pin Assignments - Siemens FS720 Quick Reference For Components / Pin Assignment

Fire detection system
Table of Contents

Advertisement

Periphery board (1-loop) FCI2001-A1
Element
Fuses
Adjustment elements
8.2

Pin assignments

8.2.1
X1 supply
38
Building Technologies
Fire Safety & Security Products
Des.
Function
H113
(H100, H101, H114, H115 not used)
H114
Not used
H115
Not used
F400
Horn output (1 A/T); Schurter OMT 125
F401
Supply output 1 (1 A/T); Schurter OMT 125
F402
Not used
F501
Monitored alarm output (1 A/T); Schurter OMT 125
F601
Monitored fault output (1 A/T); Schurter OMT 125
S100
Switchover of the LED indicators for the inputs and outputs
Inputs and outputs which are not used do not require termination.
C-NET detector lines which are not used must not be terminated.
PIN
Designation
1
#BATT
2
#CONV
3
#MAINS
4
COMMON
5
3SRC+
6
3SRC–
7
VSYS+
8
VSYS+
9
VSYS–
10
VSYS–
Admissible cable cross-section: 0.2 ... 2.5 mm²
Description
Message input from the power supply: Battery fault
Message input from the power supply: Converter fault
Message input from the power supply: Mains failure
Ground
Supply input for third supply source (+) [FR]
Supply input for third supply source (-) [FR]
Supply input from the power supply (+)
Supply input from the power supply (+)
Supply input from the power supply (–)
Supply input from the power supply (–)