Siemens FS720 Quick Reference For Components / Pin Assignment page 62

Fire detection system
Table of Contents

Advertisement

Periphery board (4 loops) FCI2004-A1
LED
Colour
Function
H108
Yellow
IO_FAULT
H109
Yellow
IO_DIR
H110
Yellow
IO_1
H111
Yellow
IO_2
H112
Yellow
IO_3
H113
Yellow
IO_4
H114
Yellow
IO_5
H115
Yellow
IO_6
H100
Yellow
IO_7
H101
Yellow
IO_8
H117
Yellow
IO_9
H118
Yellow
IO_10
H119
Yellow
IO_11
H120
Yellow
IO_12
62
Building Technologies
Fire Safety & Security Products
Indications of programmable inputs / outputs
Condition
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
STATUS
Normal operation
I/O error (excess temperature, excess voltage, etc.)
I/O STATUS (push button S100)
I/O DIRECTION (push button S100)
High input (default)
Low input
High input (default)
Low input
High input (default)
Low input
High input (default)
Low input
High input (default)
Low input
High input (default)
Low input
High input (default)
Low input
High input (default)
Low input
High input (default)
Low input
High input (default)
Low input
High input (default)
Low input
High input (default)
Low input
DIRECTION
INPUT (default)
OUTPUT
INPUT (default)
OUTPUT
INPUT (default)
OUTPUT
INPUT (default)
OUTPUT
INPUT (default)
OUTPUT
INPUT (default)
OUTPUT
INPUT (default)
OUTPUT
INPUT (default)
OUTPUT
INPUT (default)
OUTPUT
INPUT (default)
OUTPUT
INPUT (default)
OUTPUT
INPUT (default)
OUTPUT
A6V10210410_a_en_--
18.05.2009

Advertisement

Table of Contents
loading

Table of Contents