Mimic display driver FT2001-A1
25.3

Indications

LED
Colour
Function
LED_1
(Green)
Operating LED
(X8)
H201
Yellow
Update mode
25.4

Adjustment elements

Switch
Function
S200-1
Firmware update mode
S200-2
Not connected
124
Building Technologies
Fire Safety & Security Products
Condition
Meaning
Lit up
Normal condition
Fast flashing
Communication error C-NET or degraded mode of the control
(0.5 s)
panel
Slow flashing
Voltage error of the external supply or not yet configured
(1 s)
Off
Normal status (update mode inactive)
Flashes
Update mode active
DIP switch S200 activates update mode manually via the MC-Link connection.
Firmware update mode is generally started automatically and the switch S200 does
not have to be changed over. If update mode is not started automatically, it is
possible to switch over manually with S200.
Position
Meaning
ON
Update mode active
OFF
Update mode inactive