Application; Compatibility; Adjustment Functions/Selection Of The Parameter Sets - Siemens Cerberus DOTE1152 Technical Description

Multi criteria smoke detector, interactive
Table of Contents

Advertisement

10

Application

10.1

Compatibility

10.2

Adjustment functions/Selection of the parameter sets

DOTE1152
Parameter set
Risk exposure and influence
Low to moderate concentration of valuable property;
APS204SE
direct danger to persons possible; no ban on smo-
!
king.
Low to moderate concentration of valuable property;
direct danger to persons possible; no ban on smo-
APS207SE
king.
Low to high concentration of valuable property; di-
APS213SE
rect danger to persons likely; no ban on smoking.
(Default)
High concentration of valuable property; danger to
APS216SE
persons. Ban on smoking, no thermal influences.
10.3
Application
Fire & Security Products
Siemens Building Technologies Group
Fire detection system:
Control unit:
Base:
The detector is produced in the version DOTE1152A only.
No mechanical adjustment is possible on the detectors. All function changes are in-
itiated remotely by the control unit. The factory programs all detectors with a basic
parameter set. This ensures that each detector is fully functional when it is installed.
The additional parameter sets can be programmed in the field with the service PC by
downloading them from the control unit.
The parameter sets listed here are arranged in order of sensitivity (APS216 is the
most sensitive).
For planning and project planning see «Application guidelines», document e1225,
manual DS11, section 10. The detectors DOTE1152 are principally used for the
same applications as the DOT115x PolyRex detectors.
see notes chapter 2.1
Due to their EN54 compliance the PolyRex detectors DOTE1152 can be used as
universal detectors. The recommended monitoring areas, distance between detec-
tors etc. can be found in the national guidelines, the Cerberus Planning and applica-
tion guidelines (CRP), or the Security Guide. For the DOTE1152 detectors, the same
monitoring areas, distances between detectors etc. apply as for smoke detectors
(DO and DOT).
The DOTE1152 must be exclusively used as a fire detector. No CO gas warning is
possible, as the detector always evaluates the measured CO values together with
other values measured and analyses them only for the early detection of fires.
S11 AlgoRex
CC11
DB1151A
Behavior
very robust
robust
standard
sensitive
Examples
Kitchen, water vapour,
industrial applications with
possible CO emission
Water vapour, hotel rooms,
spinnery, joiner's work-
shop, industry and trade wi-
thout CO emission, food indus-
try
Museums, libraries, EDP,
hotel corridors, industry,
spinnery, joiner's work-
shop, high rooms
Medical care, clean rooms,
EDP, clean production
e4070e
10.2002