Indications - Siemens FS720 Quick Reference For Components / Pin Assignment

Fire detection system
Table of Contents

Advertisement

Networking module (SAFEDLINK) FN2001-A1
15.3

Indications

LED
Colour
Function
H1
Green
Condition of the
networking module
(SAFEDLINK)
H2
Yellow
Condition of the line 1
(A1, B1)
H3
Yellow
Condition of the line 2
(A2, B2)
78
Building Technologies
Fire Safety & Security Products
Cabling of 1 networking module
C-WEB
FCM720x
X13
A1
B1
4
3
X3
FN2001
Cabling of 2 networking modules
The main module must always be plugged in slot X13 of the operating unit
FCM72xx.
When two networking modules are used, the degraded mode module must be
plugged in slot X12 of the FCM72xx operating unit.
Condition
Off
On
Flashes
Off
On
Off
On
A2
B2
2
1
FN2001
Meaning
Networking module (SAFEDLINK) is defective
Normal condition (H2 and H3 are off)
Normal condition for degraded mode module (H2 and H3
are off)
Normal condition
(communication on line 1 is OK)
Error on line 1;
(no communication on line 1)
Normal condition
(communication on line 2 is OK)
Error on line 2;
(no communication on line 2)
A1
B1
A2
B2
4
3
2
1
X3
A6V10210410_a_en_--
18.05.2009
C-WEB